FurnaceTallyInput BTU, output BTU, and the gap nobody explains.

Furnace BTU Sizing

Input against output, and how much of the label you actually get.

6 articles

What size furnace for 2000 square feet in zone 4 at 90% AFUE

2,000 ft² in zone 4, 90% AFUE
100,000BTU/hr input
delivers 90,000 BTU/hr into the house — the house needs 86,000
2,000 ft² in zone 4, 90% AFUE100,000 BTU/hrFurnace to buy (i…90,000 BTU/hrHeat actually del…86,000 BTU/hrHeat the house ne…
Furnace to buy (input)the number printed on the box100,000BTU/hr
Heat actually delivered (output)100,000 × 90% AFUE90,000BTU/hr
Heat the house needs2,000 ft² × 43 BTU/ft² output86,000BTU/hr
Oversize5%
Same box at 80% AFUE would deliver10,000 BTU/hr less — why you resize when you upgrade80,000BTU/hr
Efficiencycondensing, PVC venting and a condensate drain90% AFUE

Notes

  • Input and output are different numbers, and the box shows the bigger one. A 100,000 BTU furnace at 90% AFUE puts 90,000 BTU/hr into the house. Compare furnaces on output, or you are comparing how much gas they burn rather than how much heat you get.
  • Upgrading efficiency without resizing is the classic error. Replace an 80% furnace with a 96% one of the same input and the house receives 16,000 BTU/hr more than it did — roughly 20% extra. The new furnace short cycles, the house swings warm and cool, and the owner concludes high efficiency is uncomfortable. It was the sizing.
  • 5% over is the normal rounding step — furnaces come in 20,000 BTU increments, so landing exactly on the calculated load is impossible.
  • These BTU-per-square-foot figures assume average insulation. A tight house with good windows can need a third less; a 1950s house with an uninsulated attic and single glazing can need a third more. The figure above is where the conversation starts.
  • A Manual J is what turns this into a specification. It accounts for window area and orientation, air leakage, insulation, ceiling height and duct losses. On a furnace it matters more than on air conditioning, because heating loads vary more between houses than cooling loads do.
  • Do not size by what was there before. The old furnace was very likely oversized too — contractors have rounded up for decades — and copying its input perpetuates the error into another twenty-year appliance.

Open the full page for this calculation →

Furnace BTU by area, climate and AFUE

360 calculations · browse all