FurnaceTallyInput BTU, output BTU, and the gap nobody explains.

Furnace BTU Sizing

Input against output, and how much of the label you actually get.

What size furnace for 2000 square feet in zone 4 at 90% AFUE

2,000 ft² in zone 4, 90% AFUE
100,000BTU/hr input
delivers 90,000 BTU/hr into the house — the house needs 86,000
2,000 ft² in zone 4, 90% AFUE100,000 BTU/hrFurnace to buy (i…90,000 BTU/hrHeat actually del…86,000 BTU/hrHeat the house ne…
Furnace to buy (input)the number printed on the box100,000BTU/hr
Heat actually delivered (output)100,000 × 90% AFUE90,000BTU/hr
Heat the house needs2,000 ft² × 43 BTU/ft² output86,000BTU/hr
Oversize5%
Same box at 80% AFUE would deliver10,000 BTU/hr less — why you resize when you upgrade80,000BTU/hr
Efficiencycondensing, PVC venting and a condensate drain90% AFUE

Notes

  • Input and output are different numbers, and the box shows the bigger one. A 100,000 BTU furnace at 90% AFUE puts 90,000 BTU/hr into the house. Compare furnaces on output, or you are comparing how much gas they burn rather than how much heat you get.
  • Upgrading efficiency without resizing is the classic error. Replace an 80% furnace with a 96% one of the same input and the house receives 16,000 BTU/hr more than it did — roughly 20% extra. The new furnace short cycles, the house swings warm and cool, and the owner concludes high efficiency is uncomfortable. It was the sizing.
  • 5% over is the normal rounding step — furnaces come in 20,000 BTU increments, so landing exactly on the calculated load is impossible.
  • These BTU-per-square-foot figures assume average insulation. A tight house with good windows can need a third less; a 1950s house with an uninsulated attic and single glazing can need a third more. The figure above is where the conversation starts.
  • A Manual J is what turns this into a specification. It accounts for window area and orientation, air leakage, insulation, ceiling height and duct losses. On a furnace it matters more than on air conditioning, because heating loads vary more between houses than cooling loads do.
  • Do not size by what was there before. The old furnace was very likely oversized too — contractors have rounded up for decades — and copying its input perpetuates the error into another twenty-year appliance.

Open the full page for this calculation