What size furnace does a 3000 sq ft house in Newark, NJ need?

3,000 ft² in Newark, NJ — 96% AFUE
140,000BTU/hr input
134,400 BTU/hr actually delivered — sized from a 11°F design day
3,000 ft² in Newark, NJ — 96% AFUE140,000 BTU/hrFurnace input rat…134,400 BTU/hrHeat actually del…134,400 BTU/hrCalculated heat l…925 thermsGas used per heat…
Furnace input rating to buy140,000BTU/hr
Heat actually delivered140,000 × 96% AFUE — the number that heats the house134,400BTU/hr
Calculated heat loss3,000 ft² × 44.8 BTU/ft²134,400BTU/hr
Winter design temperature99% design dry bulb, 2015–2024 — colder on about 4 days a year11°F
Design temperature difference70°F indoors against 11°F outdoors — this sets the whole calculation59°F
Heat loss per square foot9.4 + 0.60 × 59°F44.8BTU/ft²
Heating degree daysbase 65°F, annual average4,334°F-days
Nights at or below freezing72nights/yr
Gas used per heating seasonfrom measured household consumption, not from the sizing figure above925therms
Heating cost per yearat $1.42/therm, the national residential average$1,314
Oversize after rounding upwithin the normal step0%
Same house at a 35°F design day91,200BTU/hr
Same house at a −20°F design day2.09× spread for the identical building190,200BTU/hr

Notes

  • Newark designs to 11°F, and that single number drives everything above. Heat loss is very close to a straight line in the indoor–outdoor difference, so a 59°F design difference gives 44.8 BTU per square foot per hour. The same house needs 91 MBH on a 35°F design day and 190 MBH at −20°F — a factor of 2.09, which is why a national "40 BTU per square foot" figure is useless in both directions.
  • Two BTU numbers, and the box shows the bigger one. A 140,000 BTU/hr furnace at 96% AFUE puts 134,400 BTU/hr into the house; the rest goes up the flue. condensing, the common high-efficiency tier. The mistake to avoid is keeping the old input rating when moving to a higher efficiency — swapping an 80% unit for a 96% unit at the same input adds 22,400 BTU/hr of delivered heat the house never asked for.
  • Oversizing is the expensive mistake, not undersizing. An oversized furnace satisfies the thermostat in a few minutes, shuts off, and repeats — hard on the heat exchanger and the igniter, and it leaves the house with hot-then-cold swings and cold rooms at the ends of the duct runs. Undersizing costs comfort on the four coldest nights of the year; oversizing costs comfort on all of them.
  • Fuel, roughly — and it does not come from the number above. 4,334 heating degree days on a 3,000 ft² house works out to about 925 therms a season, 1,314 dollars at the national average gas price. That figure is calibrated against what households actually burn, not scaled from the sizing rule of thumb — and the two disagree by a factor of about 2.7, because the sizing table is deliberately conservative. Going from 80% to 96% AFUE here saves roughly $263 a year against an installed price difference usually in the $1,000–2,000 range, so the payback is a real calculation and not an obvious yes.
  • This is a heat loss estimate, not a Manual J. The real one counts window area and orientation, insulation R-values, measured air leakage, ceiling height, duct location and how many people live in the house. A tight new build in Newark can come in a third below this figure; a 1950s house with original windows and no wall insulation can come in a third above. Ask for the Manual J before signing — it costs a few hundred dollars on a $5,000–10,000 installation, and it is the only thing that turns the number above into a specification.
  • Where the design temperature comes from. It is the 1st percentile of daily low temperatures at Newark Airport, 6 km from downtown Newark, over 2015–2024 — the same kind of airport station ASHRAE measures at. The percentile was calibrated against eight airports with published ASHRAE values and reproduces them to within 2.2°F on average. Expect a degree or two of difference from a printed table; that is far smaller than the uncertainty in the house itself.

The short answer

A 3000 square foot house in Newark, NJ needs a furnace rated about 140,000 BTU per hour of input at 96% AFUE, which delivers 134,400 BTU/hr into the house.

Where that number comes from

Newark, NJ designs to 11°F — the temperature it drops below on roughly four nights a year. Against 70°F indoors that is a 59°F difference, and heat loss is very nearly a straight line in that difference: 44.8 BTU per square foot per hour here.

This is the reason a single national "40 BTU per square foot" figure is wrong in both directions. The same house wants 91,200 BTU/hr where the design night is 35°F and 190,200 BTU/hr where it is −20°F.

Input is not output

The rating on the box is fuel burned, not heat delivered. At 96% AFUE a 140,000 BTU/hr furnace puts 134,400 BTU/hr into the rooms. Keeping the old input rating when moving to a higher efficiency is the most common way a replacement ends up oversized.

What it costs to run

Newark, NJ runs 4,334 heating degree days a year. This house at 96% AFUE burns roughly 925 therms a season — about $1,314 at the national average gas price.

Before you buy

Ask for the Manual J. A few hundred dollars on a five-figure installation, and it is the only thing that turns the estimate above into a specification.