What size furnace does a 3000 sq ft house in La Crosse, WI need?
| Furnace input rating to buy | 140,000BTU/hr |
|---|---|
| Heat actually delivered140,000 × 96% AFUE — the number that heats the house | 134,400BTU/hr |
| Calculated heat loss3,000 ft² × 58 BTU/ft² | 174,000BTU/hr |
| Winter design temperature99% design dry bulb, 2015–2024 — colder on about 4 days a year | -11°F |
| Design temperature difference70°F indoors against -11°F outdoors — this sets the whole calculation | 81°F |
| Heat loss per square foot9.4 + 0.60 × 81°F | 58BTU/ft² |
| Heating degree daysbase 65°F, annual average | 6,544°F-days |
| Nights at or below freezing | 134nights/yr |
| Gas used per heating seasonfrom measured household consumption, not from the sizing figure above | 1,397therms |
| Heating cost per yearat $1.42/therm, the national residential average | $1,984 |
| Oversize after rounding upwithin the normal step | -23% |
| Same house at a 35°F design day | 91,200BTU/hr |
| Same house at a −20°F design day2.09× spread for the identical building | 190,200BTU/hr |
Notes
- La Crosse designs to -11°F, and that single number drives everything above. Heat loss is very close to a straight line in the indoor–outdoor difference, so a 81°F design difference gives 58 BTU per square foot per hour. The same house needs 91 MBH on a 35°F design day and 190 MBH at −20°F — a factor of 2.09, which is why a national "40 BTU per square foot" figure is useless in both directions.
- Two BTU numbers, and the box shows the bigger one. A 140,000 BTU/hr furnace at 96% AFUE puts 134,400 BTU/hr into the house; the rest goes up the flue. condensing, the common high-efficiency tier. The mistake to avoid is keeping the old input rating when moving to a higher efficiency — swapping an 80% unit for a 96% unit at the same input adds 22,400 BTU/hr of delivered heat the house never asked for.
- Oversizing is the expensive mistake, not undersizing. An oversized furnace satisfies the thermostat in a few minutes, shuts off, and repeats — hard on the heat exchanger and the igniter, and it leaves the house with hot-then-cold swings and cold rooms at the ends of the duct runs. Undersizing costs comfort on the four coldest nights of the year; oversizing costs comfort on all of them.
- Fuel, roughly — and it does not come from the number above. 6,544 heating degree days on a 3,000 ft² house works out to about 1,397 therms a season, 1,984 dollars at the national average gas price. That figure is calibrated against what households actually burn, not scaled from the sizing rule of thumb — and the two disagree by a factor of about 2.5, because the sizing table is deliberately conservative. Going from 80% to 96% AFUE here saves roughly $397 a year against an installed price difference usually in the $1,000–2,000 range, so the payback is a real calculation and not an obvious yes.
- This is a heat loss estimate, not a Manual J. The real one counts window area and orientation, insulation R-values, measured air leakage, ceiling height, duct location and how many people live in the house. A tight new build in La Crosse can come in a third below this figure; a 1950s house with original windows and no wall insulation can come in a third above. Ask for the Manual J before signing — it costs a few hundred dollars on a $5,000–10,000 installation, and it is the only thing that turns the number above into a specification.
- Where the design temperature comes from. It is the 1st percentile of daily low temperatures at La Crosse Municipal Airport, 9 km from downtown La Crosse, over 2015–2024 — the same kind of airport station ASHRAE measures at. The percentile was calibrated against eight airports with published ASHRAE values and reproduces them to within 2.2°F on average. Expect a degree or two of difference from a printed table; that is far smaller than the uncertainty in the house itself.
The short answer
A 3000 square foot house in La Crosse, WI needs a furnace rated about 140,000 BTU per hour of input at 96% AFUE, which delivers 134,400 BTU/hr into the house.
Where that number comes from
La Crosse, WI designs to -11°F — the temperature it drops below on roughly four nights a year. Against 70°F indoors that is a 81°F difference, and heat loss is very nearly a straight line in that difference: 58 BTU per square foot per hour here.
This is the reason a single national "40 BTU per square foot" figure is wrong in both directions. The same house wants 91,200 BTU/hr where the design night is 35°F and 190,200 BTU/hr where it is −20°F.
Input is not output
The rating on the box is fuel burned, not heat delivered. At 96% AFUE a 140,000 BTU/hr furnace puts 134,400 BTU/hr into the rooms. Keeping the old input rating when moving to a higher efficiency is the most common way a replacement ends up oversized.
What it costs to run
La Crosse, WI runs 6,544 heating degree days a year. This house at 96% AFUE burns roughly 1,397 therms a season — about $1,984 at the national average gas price.
Before you buy
Ask for the Manual J. A few hundred dollars on a five-figure installation, and it is the only thing that turns the estimate above into a specification.
Nearby sizes
- What size furnace does a 3000 sq ft house in Lenexa, KS need?
- What size furnace does a 3000 sq ft house in Albany, OR need?
- What size furnace does a 3000 sq ft house in Downtown DC, DC need?
- What size furnace does a 3000 sq ft house in Enid, OK need?
- What size furnace does a 2800 sq ft house in La Crosse, WI need?
- What size furnace does a 3500 sq ft house in La Crosse, WI need?
- What size furnace does a 2600 sq ft house in La Crosse, WI need?
- What size furnace does a 4000 sq ft house in La Crosse, WI need?
Read more
- Five Signs the Furnace Is Too Big for the HouseThe furnace heats the house quickly and then stops. That is the complaint, even though it sounds like a compliment.
- What Size Furnace — BTU Per Square Foot, and Why Input Is Not OutputA 100,000 BTU furnace at 80% AFUE delivers 80,000. Sizing against the wrong one of those two numbers is a 25% error before anything else goes wrong.
- The New Furnace Has to Live in the Old DuctworkThe equipment is chosen from a catalogue. The ducts are whatever the house already has, and they decide what the equipment can deliver.
- Insulating the House Changes the Furnace It NeedsEvery improvement to the envelope is a reduction in required BTU, and it only counts if the sizing happens afterwards.