FurnaceTallyInput BTU, output BTU, and the gap nobody explains.

What size furnace does a 1400 sq ft house in Appleton, WI need?

1,400 ft² in Appleton, WI — 96% AFUE
100,000BTU/hr input
96,000 BTU/hr actually delivered — sized from a -8°F design day
1,400 ft² in Appleton, WI — 96% AFUE100,000 BTU/hrFurnace input rat…96,000 BTU/hrHeat actually del…78,680 BTU/hrCalculated heat l…701 thermsGas used per heat…
Furnace input rating to buy100,000BTU/hr
Heat actually delivered100,000 × 96% AFUE — the number that heats the house96,000BTU/hr
Calculated heat loss1,400 ft² × 56.2 BTU/ft²78,680BTU/hr
Winter design temperature99% design dry bulb, 2015–2024 — colder on about 4 days a year-8°F
Design temperature difference70°F indoors against -8°F outdoors — this sets the whole calculation78°F
Heat loss per square foot9.4 + 0.60 × 78°F56.2BTU/ft²
Heating degree daysbase 65°F, annual average7,034°F-days
Nights at or below freezing142nights/yr
Gas used per heating seasonfrom measured household consumption, not from the sizing figure above701therms
Heating cost per yearat $1.42/therm, the national residential average$995
Oversize after rounding upa full size step above the load — see the note22%
Same house at a 35°F design day42,560BTU/hr
Same house at a −20°F design day2.09× spread for the identical building88,760BTU/hr

Notes

  • Appleton designs to -8°F, and that single number drives everything above. Heat loss is very close to a straight line in the indoor–outdoor difference, so a 78°F design difference gives 56.2 BTU per square foot per hour. The same house needs 43 MBH on a 35°F design day and 89 MBH at −20°F — a factor of 2.09, which is why a national "40 BTU per square foot" figure is useless in both directions.
  • Two BTU numbers, and the box shows the bigger one. A 100,000 BTU/hr furnace at 96% AFUE puts 96,000 BTU/hr into the house; the rest goes up the flue. condensing, the common high-efficiency tier. The mistake to avoid is keeping the old input rating when moving to a higher efficiency — swapping an 80% unit for a 96% unit at the same input adds 16,000 BTU/hr of delivered heat the house never asked for.
  • 100,000 BTU/hr is 22% above the calculated loss. Input ratings step in 20,000 BTU jumps and there is nothing in between, so this house lands well up the step. A two-stage or modulating furnace fixes it properly: it runs long, low and quiet at part load instead of firing full-tilt for eight minutes and stopping. Single-stage equipment at this size will short cycle through most of the winter.
  • Fuel, roughly — and it does not come from the number above. 7,034 heating degree days on a 1,400 ft² house works out to about 701 therms a season, 995 dollars at the national average gas price. That figure is calibrated against what households actually burn, not scaled from the sizing rule of thumb — and the two disagree by a factor of about 2.5, because the sizing table is deliberately conservative. Going from 80% to 96% AFUE here saves roughly $199 a year against an installed price difference usually in the $1,000–2,000 range, so the payback is a real calculation and not an obvious yes.
  • This is a heat loss estimate, not a Manual J. The real one counts window area and orientation, insulation R-values, measured air leakage, ceiling height, duct location and how many people live in the house. A tight new build in Appleton can come in a third below this figure; a 1950s house with original windows and no wall insulation can come in a third above. Ask for the Manual J before signing — it costs a few hundred dollars on a $5,000–10,000 installation, and it is the only thing that turns the number above into a specification.
  • Where the design temperature comes from. It is the 1st percentile of daily low temperatures at Austin Straubel International Airport, 33 km from downtown Appleton, over 2015–2024 — the same kind of airport station ASHRAE measures at. The percentile was calibrated against eight airports with published ASHRAE values and reproduces them to within 2.2°F on average. Expect a degree or two of difference from a printed table; that is far smaller than the uncertainty in the house itself.

The short answer

A 1400 square foot house in Appleton, WI needs a furnace rated about 100,000 BTU per hour of input at 96% AFUE, which delivers 96,000 BTU/hr into the house.

Where that number comes from

Appleton, WI designs to -8°F — the temperature it drops below on roughly four nights a year. Against 70°F indoors that is a 78°F difference, and heat loss is very nearly a straight line in that difference: 56.2 BTU per square foot per hour here.

This is the reason a single national "40 BTU per square foot" figure is wrong in both directions. The same house wants 42,560 BTU/hr where the design night is 35°F and 88,760 BTU/hr where it is −20°F.

Input is not output

The rating on the box is fuel burned, not heat delivered. At 96% AFUE a 100,000 BTU/hr furnace puts 96,000 BTU/hr into the rooms. Keeping the old input rating when moving to a higher efficiency is the most common way a replacement ends up oversized.

What it costs to run

Appleton, WI runs 7,034 heating degree days a year. This house at 96% AFUE burns roughly 701 therms a season — about $995 at the national average gas price.

Before you buy

Ask for the Manual J. A few hundred dollars on a five-figure installation, and it is the only thing that turns the estimate above into a specification.

Nearby sizes

Read more